Effectiveness of chilled ceiling assisted by intermittent personalized ventilation for active contaminants’ confinement and energy savings

Loading...
Thumbnail Image

Date

Journal Title

Journal ISSN

Volume Title

Publisher

European Association for the Development of Renewable Energy, Environment and Power Quality (EA4EPQ)

Abstract

The integration of intermittent personalized ventilation in office spaces equipped with chilled ceiling has been proven to enhance comfort and provide satisfactory indoor air quality. However, in the case where the occupant using the personalized ventilator is infected, the turbulence of the intermittent personalized ventilation jet could enhance contaminant spread and compromise the indoor air quality in the space. In this work, an office space equipped with a chilled ceiling and intermittent personalized ventilation was modelled using a validated CFD model. The intermittent jet was supplied towards an infected occupant. The frequency and average flow rate that could minimize particle spread in the space were investigated. It was found that the intermittent personalized ventilator should be operated at a frequency of 0.3 Hz and an average flow rate of 3.5 L/s. These conditions confined the particles to their source of generation while still providing comfort for the infected occupant. © 2019, European Association for the Development of Renewable Energy, Environment and Power Quality (EA4EPQ). All rights reserved.

Description

Keywords

Active contaminants, Chilled ceiling, Energy savings, Personalized ventilation

Citation

Endorsement

Review

Supplemented By

Referenced By