Performance of combined displacement ventilation and cooled ceiling liquid desiccant membrane system in Beirut climate

Loading...
Thumbnail Image

Date

Journal Title

Journal ISSN

Volume Title

Publisher

Taylor and Francis Ltd.

Abstract

The performance of the chilled ceiling (CC) displacement ventilation (DV) systems is constrained by latent load removal capacity and cost of supply air dehumidification to prevent condensation on the ceiling. In this study, a liquid desiccant dehumidification membrane cycle (LDMC) is mathematically modelled to replace the CC and remove directly latent and sensible load from indoor space through the membrane. The desiccant system is coupled with the DV system. An optimized operational strategy is adopted while allowing ceiling temperature to drop to lower values than conventional CC/DV. The optimized LDMC-C/DV system was implemented in an office space in Beirut climate. It was found that decreasing the membrane liquid desiccant temperature resulted in a significant decrease in the total cooling energy of the system, while increasing the solar heating energy of the desiccant regeneration. At optimal set points, a decrease of 49% in energy consumption was observed compared to the conventional CC/DV system. © 2016 International Building Performance Simulation Association (IBPSA).

Description

Keywords

Chilled ceiling, Displacement ventilation, Energy efficiency, Indoor air quality, Liquid desiccant membrane, Optimization, Air quality, Ceilings, Driers (materials), Energy utilization, Humidity control, Indoor air pollution, Liquids, Membranes, Office buildings, Air dehumidification, Ceiling temperatures, Liquid desiccant, Operational strategies, Removal capacity, Ventilation

Citation

Endorsement

Review

Supplemented By

Referenced By