Design charts for sizing CC/DV system aided with personalized evaporative cooler to the desired thermal comfort

dc.contributor.authorMirzaie, Sahar
dc.contributor.authorGhaddar, Nesreen K.
dc.contributor.authorGhali, Kamel Abou
dc.contributor.authorKeblawi, Amer
dc.contributor.departmentDepartment of Mechanical Engineering
dc.contributor.facultyMaroun Semaan Faculty of Engineering and Architecture (MSFEA)
dc.contributor.institutionAmerican University of Beirut
dc.date.accessioned2025-01-24T11:32:03Z
dc.date.available2025-01-24T11:32:03Z
dc.date.issued2015
dc.description.abstractThis work extends chilled ceiling displacement ventilation (CC/DV) design charts to a wider operation range of DV supply temperatures and flow rates when aided with personalized evaporative cooler (PEC) at typical office of peak load of 70 W/m2. The overall thermal comfort (OTC) of the occupant can be read off from the chart at different operating conditions of DV/CC-PEC system. The charts simplify the sizing procedure of the CC/DV-PEC system by specifying the operational design parameters which include temperatures of DV supply and CC surface, PEC airflow rate, the ratio of total load over DV airflow rate named displaced air parameter (P), and the CC cooling load. In producing the charts, extensive simulations were performed using a multilayer space thermal model to determine the human microenvironment conditions and local comfort models to determine occupant thermal comfort. The use of the charts is demonstrated through case studies. It is found that the addition of PEC at flow rate of 10 l/s provided acceptable thermal comfort up to DV supply temperature of 26 °C. In such conditions, the CC/DV heat removal is about 83% of the space baseline load in design conditions which leads to energy savings while maintaining comfort. © 2014 Elsevier B.V. All rights reserved.
dc.identifier.doihttps://doi.org/10.1016/j.enbuild.2014.09.084
dc.identifier.eid2-s2.0-84908378343
dc.identifier.urihttp://hdl.handle.net/10938/27666
dc.language.isoen
dc.publisherElsevier Ltd
dc.relation.ispartofEnergy and Buildings
dc.sourceScopus
dc.subjectChilled ceiling
dc.subjectDesign chart
dc.subjectDisplacement ventilation
dc.subjectPersonalized evaporative cooler
dc.subjectThermal comfort
dc.subjectComputer simulation
dc.subjectCooling systems
dc.subjectDesign
dc.subjectEnergy conservation
dc.subjectFlow rate
dc.subjectVentilation
dc.subjectDesign charts
dc.subjectDifferent operating conditions
dc.subjectEvaporative coolers
dc.subjectExtensive simulations
dc.subjectOverall thermal comforts
dc.subjectSupply temperatures
dc.subjectGraphic methods
dc.titleDesign charts for sizing CC/DV system aided with personalized evaporative cooler to the desired thermal comfort